Rheem 62-24140-04 Control Board Canada
Furnace Control Control - replacement for Rheem 62-24140-04 control boards
Specifications:
Control Voltage: 24 VAC (18-30 VAC), 60Hz
Line Voltage: 115 VAC, 60Hz
Timing:
- Pre-Purge: 30 seconds
- Trial for Ignition: 7 seconds
- Retries: Two groups of two, 30 second delay within the group, and 3 minute delay between groups
- Lockout: 1-hour
- Post-Purge: 90, 120, 160 and 180 seconds
Inputs:
- Power: 24 VAC and COM
- Thermostat Interface: R,W, Y, and G
- System Switches: Vent pressure and limit switches (main and over-temperature switches in series)
- Flame Sensing
- Heat Blower OFF Delay (miniature slide switch set)
Outputs:
- Spark
- Gas Valve: GV
- Inducer Draft Motor: IDM
- Blower Motor: FAN, COOL and HEAT speeds
- Electric air Cleaner: EAC
- Humidifier Relay: HUM
- Heat/Cool Relay: H/C
LED Indicators:
- Power, Green LED: PWR
- Status, Green LED: OK
- Flame Status, Yellow LED: FLAME
Patents:
- #6,222,719: Ignition Boost
- #5,917,691: Fail Safe Relay Driver
Weight/Dimensions:
- Weight: 0.6
- Height: 2.5
- Width: 6.625
- Length: 5.75
Rheem 62-24140-04, Rheem 62-24140-02, RHEEM 62-24136-01, 62-24140-01, 62-24140-02, 62-24140-02, 62-24140-04, 62-24141-02, 1028-928,
62-24140-04, 622414004, 62-24136-01, 622413601, 62-24136-02, 622413602, 62-24136-03, 622413603, 62-24140-01, 622414001, 62-24140-02, 622414002,
62-24141-01, 622414101, 1028-927, 62-24140-04, 62-262697-01, 62-24140-2, 62-24136-01, G691DAJ-240, G961BAJ-240H, 62-24136-10, 62-24136-02, 62-24136-03,
62-24140-01, 62-24140-02, 62-24141-01, G961DAJ-2402, 622413610, 622413602, 622413603, 622414001, 622414002, 622414101, 622413602, 62-24140-01,
1028-83-928D, G961DAG-2401, 62-24140-04, 622414002, 1028-928 1028-928-I, 62-24140-02, CAR622414001, CAR622414004, 62-23543-01